Assessment Year 2012
Principal Product Automotive Hand tools
NAICS 339999: All Other Miscellaneous Manufacturing
SIC 3423: Hand and Edge Tools, Except Machine Tools and Handsaws
Sales Range $10
M
to 50
M
# of Employees 230
Plant Area 248,500
ft2
Annual Production 0
units
Production Hrs. Annual 6,000
hrs
Location (State) Iowa

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $101,967 2,876,000
kWh
Electricity Demand $43,490 9,312
kW-mo/yr
Electricity Fees $30,761 -
Natural Gas $276,767 58,142
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $10,889 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $2,985 $8,240 $2,414
55,480
kWh
$571
-
kW-mo/yr
02 2.7142: Utilize higher efficiency lamps and/or ballasts $1,402 $1,618 $853
19,600
kWh
$549
-
kW-mo/yr
03 2.7135: Install occupancy sensors $1,963 $1,193 $1,963
45,137
kWh
-
04 2.4221: Install compressor air intakes in coolest locations $1,615 $753 $1,332
30,552
kWh
$283
-
kW-mo/yr
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,152 $249 $1,772
40,740
kWh
$380
-
kW-mo/yr
06 2.4239: Eliminate or reduce compressed air usage $772 $285 $772
17,725
kWh
-
TOTAL RECOMMENDED $10,889 $12,338 $9,106
209,234
kWh
$1,783
-
kW-mo/yr
TOTAL IMPLEMENTED - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs