Assessment Year | 2012 |
---|---|
Principal Product | Plastic Film Bags |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $10 M to 50M |
# of Employees | 35 |
Plant Area |
50,000
ft2
|
Annual Production | 15,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | South Dakota |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $144,874 | 4,689,300 |
kWh
|
$0.031 |
Electricity Demand | $114,942 | 8,823 |
kW-mo/yr
|
$13.03 |
Electricity Fees | $690 | - |
|
- |
LPG | $10,258 | 491 |
MMBtu
|
$20.89 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,774 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,182 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,228 | $574 |
$2,677
86,636
kWh
|
$1,551
-
kW-mo/yr
|
|
02 | 2.4221: Install compressor air intakes in coolest locations | $1,468 | $1,000 |
$922
29,788
kWh
|
$546
-
kW-mo/yr
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $599 | $50 |
$379
12,264
kWh
|
$220
-
kW-mo/yr
|
|
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,687 | $825 |
$1,060
34,340
kWh
|
$627
-
kW-mo/yr
|
|
05 | 2.7111: Reduce illumination to minimum necessary levels | $2,452 | $192 |
$1,624
52,560
kWh
|
$828
-
kW-mo/yr
|
|
06 | 2.7135: Install occupancy sensors | $1,174 | $460 |
$1,174
38,001
kWh
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,668 | $1,668 |
$1,033
33,424
kWh
|
$635
-
kW-mo/yr
|
|
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $19,498 | $18,823 |
$12,411
401,637
kWh
|
$7,087
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $32,774 | $23,592 |
$21,280
688,650
kWh
|
$11,494
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $8,182 | $3,117 |
$5,149
166,664
kWh
|
$3,033
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs