Assessment Year | 2009 |
---|---|
Principal Product | CNC Precision Machined Parts |
NAICS | 332721: Precision Turned Product Manufacturing |
SIC | 5084: Industrial Machinery and Equipment |
Sales Range | $5 M to 10M |
# of Employees | 76 |
Plant Area |
34,500
ft2
|
Annual Production | 660,000
lb
|
Production Hrs. Annual | 6,292
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $57,917 | 1,468,940 |
kWh
|
$0.039 |
Electricity Demand | $20,945 | 232 |
kW-mo/yr
|
$90.28 |
Natural Gas | $20,559 | 1,896 |
MMBtu
|
$10.84 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $2,775 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,548 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,119 | $2,112 |
$820
20,763
kWh
|
$299
-
kW-mo/yr
|
- | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $241 | $200 |
$166
4,246
kWh
|
$75
-
kW-mo/yr
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $312 | $72 |
$229
11,578
kWh
|
$83
-
kW-mo/yr
|
- | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $153 | $60 |
$108
2,730
kWh
|
$45
-
kW-mo/yr
|
- | - | |
05 | 2.6218: Turn off equipment when not in use | $386 | $60 |
$386
9,784
kWh
|
- | - | - | |
06 | 2.2223: Enhance sensitivity of temperature control and cutoff | $74 | $100 | - | - |
$74
-
MMBtu
|
- | |
07 | 2.6218: Turn off equipment when not in use | $490 | $130 | - | - | - |
$490
-
Tgal
|
|
TOTAL RECOMMENDED | $2,775 | $2,734 |
$1,709
49,101
kWh
|
$502
-
kW-mo/yr
|
$74
-
MMBtu
|
$490
-
Tgal
|
||
TOTAL IMPLEMENTED | $2,548 | $2,574 |
$1,601
46,371
kWh
|
$457
-
kW-mo/yr
|
- |
$490
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs