Assessment Year | 2008 |
---|---|
Principal Product | Construction Equipment |
NAICS | 423810: Construction and Mining (except Oil Well) Machinery and Equipment Merchant Wholesalers |
SIC | 5082: Construction and Mining (Except Petroleum) Machinery and Equipment |
Sales Range | $50 M to 100M |
# of Employees | 442 |
Plant Area |
500,000
ft2
|
Annual Production | 8,500
pieces
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,615,867 | 19,390,400 |
kWh
|
$0.083 |
Electricity Demand | $640,511 | 3,760 |
kW-mo/yr
|
$170.35 |
Natural Gas | $1,237,038 | 1,366,482 |
MMBtu
|
$0.91 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $158,526 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $77,936 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,200 | $10,307 |
$6,731
2,752,964
kWh
|
$10,469
-
kW-mo/yr
|
- | - | - | |
02 | 2.7135: Install occupancy sensors | $678 | $847 |
$678
30,820
kWh
|
- | - | - | - | |
03 | 2.7144: Install spectral reflectors / delamp | $3,565 | $225 |
$1,232
56,028
kWh
|
$2,333
-
kW-mo/yr
|
- | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,748 | $2,450 |
$2,643
120,141
kWh
|
$4,105
-
kW-mo/yr
|
- | - | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,526 | $30 |
$1,771
80,522
kWh
|
$2,755
-
kW-mo/yr
|
- | - | - | |
06 | 2.8123: Pay utility bills on time | $16,112 | - | - | - | - | - | $16,112 | |
07 | 2.7444: Close holes and openings in building such as broken windows | $4,743 | $185 | - | - |
$4,743
-
MMBtu
|
- | - | |
08 | 2.7311: Ventilation system to shut off when room is not in use | $7,288 | $3,550 |
$410
18,672
kWh
|
- |
$6,878
-
MMBtu
|
- | - | |
09 | 2.7311: Ventilation system to shut off when room is not in use | $4,110 | $10,000 |
$852
38,710
kWh
|
- |
$3,258
-
MMBtu
|
- | - | |
10 | 2.3212: Optimize plant power factor | $64,666 | $43,320 | - | - | - | - | $64,666 | |
11 | 3.5217: Reuse / recycle/ sell paper products | $28,890 | $8,900 | - | - | - |
$28,890
-
lb
|
- | |
TOTAL RECOMMENDED | $158,526 | $79,814 |
$14,317
3,097,857
kWh
|
$19,662
-
kW-mo/yr
|
$14,879
-
MMBtu
|
$28,890
-
lb
|
$80,778 | ||
TOTAL IMPLEMENTED | $77,936 | $22,914 |
$11,284
2,959,953
kWh
|
$16,907
-
kW-mo/yr
|
$4,743
-
MMBtu
|
$28,890
-
lb
|
$16,112 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs