| Assessment Year | 2007 | 
|---|---|
| Principal Product | Animal Vaccines | 
| NAICS | 325414: Biological Product (except Diagnostic) Manufacturing | 
| SIC | 2836: Biological Products, Except Diagnostic Substances | 
| Sales Range | $50 Mto 100 M | 
| # of Employees | 120 | 
| Plant Area | 153,258 
ft2
 | 
| Annual Production | 47,000,000 
units
 | 
| Production Hrs. Annual | 2,375 
hrs
 | 
| Location (State) | Iowa | 
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $221,764 | 6,918,528 | 
kWh
 | $0.032 | 
| Electricity Demand | $82,162 | 13,404 | 
kW-mo/yr
 | $6.13 | 
| Electricity Fees | $7,128 | - |  | - | 
| Natural Gas | $290,325 | 30,218 | 
MMBtu
 | $9.61 | 
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $30,610 | See individual recommendations below*Non-energy impacts included in savings. | ||
| IMPLEMENTED SAVINGS* | $9,572 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | 
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,897 | $28,132 | $3,243 151,471
                                 
kWh
 | $4,654 -
                                 
kW-mo/yr
 | - | |
| 02 | 2.7135: Install occupancy sensors | $419 | $1,309 | $419 19,575
                                 
kWh
 | - | - | |
| 03 | 2.2414: Use waste heat from hot flue gases to preheat | $618 | $1,000 | - | - | $618 -
                                 
MMBtu
 | |
| 04 | 2.2163: Use minimum steam operating pressure | $833 | $150 | - | - | $833 -
                                 
MMBtu
 | |
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $911 | $1,275 | $640 29,908
                                 
kWh
 | $271 -
                                 
kW-mo/yr
 | - | |
| 06 | 2.7224: Reduce space conditioning during non-working hours | $17,816 | $1,375 | $485 22,690
                                 
kWh
 | - | $17,331 -
                                 
MMBtu
 | |
| 07 | 2.4221: Install compressor air intakes in coolest locations | $441 | $410 | $287 13,395
                                 
kWh
 | $154 -
                                 
kW-mo/yr
 | - | |
| 08 | 2.4133: Use most efficient type of electric motors | $1,675 | $33 | $1,157 54,067
                                 
kWh
 | $518 -
                                 
kW-mo/yr
 | - | |
| TOTAL RECOMMENDED | $30,610 | $33,684 | $6,231 291,106
                                 
kWh
 | $5,597 -
                                 
kW-mo/yr
 | $18,782 -
                                 
MMBtu
 | ||
| TOTAL IMPLEMENTED | $9,572 | $28,165 | $4,400 205,538
                                 
kWh
 | $5,172 -
                                 
kW-mo/yr
 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs
             
             
             
            