Assessment Year | 2003 |
---|---|
Principal Product | Frozen Peas and Corn |
NAICS | 311411: Frozen Fruit, Juice, and Vegetable Manufacturing |
SIC | 2037: Frozen Fruits, Fruit Juices, and Vegetables |
Sales Range | $10 M to 50M |
# of Employees | 115 |
Plant Area |
374,000
ft2
|
Annual Production | 57,000,000
lb
|
Production Hrs. Annual | 4,632
hrs
|
Location (State) | Minnesota |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $547,908 | 16,868,638 |
kWh
|
$0.032 |
Electricity Demand | $417,462 | 46,570 |
kW-mo/yr
|
$8.96 |
Natural Gas | $294,260 | 73,375 |
MMBtu
|
$4.01 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $50,766 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,786 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,889 | $1,000 | - | - |
$1,889
-
MMBtu
|
|
02 | 2.1213: Direct warmest air to combustion intake | $916 | $1,734 | - | - |
$916
-
MMBtu
|
|
03 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $34,175 | $36,000 | - | - |
$34,175
-
MMBtu
|
|
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $487 | $23 |
$327
10,191
kWh
|
$160
-
kW-mo/yr
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,233 | $220 |
$933
29,054
kWh
|
$300
-
kW-mo/yr
|
- | |
06 | 2.4133: Use most efficient type of electric motors | $4,040 | $99 |
$2,714
84,544
kWh
|
$1,326
-
kW-mo/yr
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,173 | $7,342 |
$2,715
84,581
kWh
|
$1,458
-
kW-mo/yr
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $866 | $1,149 |
$583
18,177
kWh
|
$283
-
kW-mo/yr
|
- | |
09 | 2.7124: Make a practice of turning off lights when not needed | $2,303 | - |
$2,303
71,756
kWh
|
- | - | |
10 | 2.7135: Install occupancy sensors | $684 | $1,064 |
$684
21,306
kWh
|
- | - | |
TOTAL RECOMMENDED | $50,766 | $48,631 |
$10,259
319,609
kWh
|
$3,527
-
kW-mo/yr
|
$36,980
-
MMBtu
|
||
TOTAL IMPLEMENTED | $13,786 | $9,897 |
$10,259
319,609
kWh
|
$3,527
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs