ITAC Assessment: IA0252
ITAC logo
ITAC Assessment: IA0252
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2000
Principal Product dairy products
NAICS
n/a
SIC 2026: Fluid Milk
Sales Range $50
M
to 100
M
# of Employees 200
Plant Area 80,000
ft2
Annual Production 250,000,000
lb
Production Hrs. Annual 7,488
hrs
Location (State) Nebraska

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $222,863 9,396,249
kWh
Electricity Demand $129,830 18,444
kW-mo/yr
Natural Gas $95,658 34,205
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $104,433 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $9,891

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
01 2.4221: Install compressor air intakes in coolest locations $2,486 $2,487 $1,678
71,805
kWh
$808
-
kW-mo/yr
- -
02 2.4231: Reduce the pressure of compressed air to the minimum required $1,923 $1,921 $1,297
55,393
kWh
$626
-
kW-mo/yr
- -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,422 $1,421 $957
41,032
kWh
$465
-
kW-mo/yr
- -
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $2,856 $2,855 $1,927
82,356
kWh
$929
-
kW-mo/yr
- -
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $2,132 $2,132 $1,015
43,083
kWh
$1,117
-
kW-mo/yr
- -
06 2.4133: Use most efficient type of electric motors $909 $775 $613
26,084
kWh
$296
-
kW-mo/yr
- -
07 2.7135: Install occupancy sensors $488 $488 $488
20,809
kWh
- - -
08 2.7142: Utilize higher efficiency lamps and/or ballasts $649 $374 $438
18,757
kWh
$211
-
kW-mo/yr
- -
09 2.1213: Direct warmest air to combustion intake $617 $617 - - $617
-
MMBtu
-
10 4.441: Install automatic packing equipment $88,850 $88,849 $(-584.0)
(-4,982)
kWh
$(-422.0)
-
kW-mo/yr
- $89,856
11 4.122: Develop standard procedures to improve internal yields $2,101 $2,101 - - - $2,101
TOTAL RECOMMENDED $104,433 $104,020 $7,829
354,337
kWh
$4,030
-
kW-mo/yr
$617
-
MMBtu
$91,957
TOTAL IMPLEMENTED $9,891 $9,478 $6,247
266,705
kWh
$3,644
-
kW-mo/yr
- -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs