Assessment Year | 2000 |
---|---|
Principal Product | fluid milk |
NAICS |
n/a
|
SIC | 2026: Fluid Milk |
Sales Range | $10 M to 50M |
# of Employees | 140 |
Plant Area |
200,000
ft2
|
Annual Production | 192,000
ton
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $425,143 | 15,078,840 |
kWh
|
$0.028 |
Electricity Demand | $167,716 | 29,112 |
kW-mo/yr
|
$5.76 |
Natural Gas | $164,883 | 65,741 |
MMBtu
|
$2.51 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $55,080 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $41,249 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings | By-product Production Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,446 | $6,216 |
$916
50,117
kWh
|
$1,530
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.7124: Make a practice of turning off lights when not needed | $6,280 | - |
$3,189
174,385
kWh
|
$3,091
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,901 | $13,746 |
$3,015
164,713
kWh
|
$2,886
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.7135: Install occupancy sensors | $1,574 | $3,390 |
$1,574
85,873
kWh
|
- | - | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,361 | - |
$1,199
65,651
kWh
|
$1,162
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.7135: Install occupancy sensors | $532 | $399 |
$532
29,015
kWh
|
- | - | - | - | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $2,508 | $95 |
$1,294
70,633
kWh
|
$1,214
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.1213: Direct warmest air to combustion intake | $2,408 | $1,400 | - | - |
$2,408
-
MMBtu
|
- | - | - | |
09 | 2.2533: Replace air curtain doors with solid doors | $2,002 | $1,058 |
$1,114
60,961
kWh
|
$888
-
kW-mo/yr
|
- | - | - | - | |
10 | 3.1291: Eliminate practice of mixing waste streams | $22,300 | $70,000 |
$(-343.0)
(-18,757)
kWh
|
$(-2,554.0)
-
kW-mo/yr
|
- | - | - | $25,197 | |
11 | 3.1191: Change procedures / equipment / operating conditions | $3,982 | $285 | - | - | - |
$2,561
-
Tgal
|
$1,421
-
Tgal
|
- | |
12 | 2.2511: Insulate bare equipment | $2,786 | $334 | - | - | - |
$1,792
-
Tgal
|
$994
-
Tgal
|
- | |
TOTAL RECOMMENDED | $55,080 | $96,923 |
$12,490
682,591
kWh
|
$8,217
-
kW-mo/yr
|
$2,408
-
MMBtu
|
$4,353
-
Tgal
|
$2,415
-
Tgal
|
$25,197 | ||
TOTAL IMPLEMENTED | $41,249 | $84,365 |
$5,861
320,341
kWh
|
$3,423
-
kW-mo/yr
|
- |
$4,353
-
Tgal
|
$2,415
-
Tgal
|
$25,197 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings | By-product Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs