Assessment Year | 1999 |
---|---|
Principal Product | Windows and Doors |
NAICS |
n/a
|
SIC | 2431: Millwork |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
100,000
ft2
|
Annual Production | 85,000
pieces
|
Production Hrs. Annual | 2,730
hrs
|
Location (State) | Minnesota |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $21,635 | 661,782 |
kWh
|
$0.033 |
Electricity Demand | $19,322 | 2,460 |
kW-mo/yr
|
$7.85 |
Natural Gas | $13,740 | 2,569 |
MMBtu
|
$5.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $70,226 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,829 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,393 | $381 |
$2,146
65,651
kWh
|
$2,247
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,198 | $9,000 |
$1,046
30,481
kWh
|
$1,152
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $988 | - |
$482
14,654
kWh
|
$506
-
kW-mo/yr
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $265 | $189 |
$126
3,810
kWh
|
$139
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $189 | $798 |
$189
5,569
kWh
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $183 | $13 |
$89
2,638
kWh
|
$94
-
kW-mo/yr
|
- | |
07 | 4.515: Install shelves / racks to utilize unused space | $55,120 | $2,500 | - | - | $55,120 | |
08 | 4.322: Eliminate old stock and modify inventory control | $6,890 | $12,000 | - | - | $6,890 | |
TOTAL RECOMMENDED | $70,226 | $24,881 |
$4,078
122,803
kWh
|
$4,138
-
kW-mo/yr
|
$62,010 | ||
TOTAL IMPLEMENTED | $5,829 | $583 |
$2,843
86,753
kWh
|
$2,986
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs