Assessment Year | 2005 |
---|---|
Principal Product | Pharmaceuticals |
NAICS | 325411: Medicinal and Botanical Manufacturing |
SIC | 2833: Medicinal Chemicals and Botanical Products |
Sales Range | n/a |
# of Employees | 500 |
Plant Area |
358,400
ft2
|
Annual Production | 999,999,999
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $570,981 | 16,846,011 |
kWh
|
$0.034 |
Electricity Demand | $456,732 | 31,975 |
kW-mo/yr
|
$14.28 |
Electricity Fees | $816 | - |
|
- |
Natural Gas | $442,511 | 64,618 |
MMBtu
|
$6.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $85,370 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $25,370 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.2437: Recover waste heat from equipment | $22,680 | $3,500 | - | - |
$22,680
-
MMBtu
|
- | - | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $14,470 | $1,000 |
$9,090
261,400
kWh
|
$5,380
-
kW-mo/yr
|
- | - | - | - | - | |
03 | 2.9112: Use solar heat to heat water | $8,940 | $108,000 | - | - |
$8,940
-
MMBtu
|
- | - | - | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,930 | $7,590 |
$3,100
88,900
kWh
|
$1,830
-
kW-mo/yr
|
- | - | - | - | - | |
05 | 3.4156: Use flow control valves on equipment to optimize water use | $2,040 | $1,980 | - | - | - |
$1,120
-
Tgal
|
- | - |
$920
-
Tgal
|
|
06 | 2.9111: Use solar heat to heat make-up air | $17,660 | $106,080 | - | - |
$17,660
-
MMBtu
|
- | - | - | - | |
07 | 2.7145: Install skylights | $9,370 | $56,000 |
$3,980
114,400
kWh
|
$4,820
-
kW-mo/yr
|
- | - | $200 | $370 | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,770 | $3,520 |
$420
12,000
kWh
|
$240
-
kW-mo/yr
|
- | - | $660 | $450 | - | |
09 | 2.7224: Reduce space conditioning during non-working hours | $1,600 | $1,980 |
$750
21,700
kWh
|
- |
$850
-
MMBtu
|
- | - | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,350 | $5,400 |
$400
11,500
kWh
|
$840
-
kW-mo/yr
|
- | - | $40 | $70 | - | |
11 | 2.7135: Install occupancy sensors | $560 | $710 |
$490
14,200
kWh
|
- | - | - | - | $70 | - | |
TOTAL RECOMMENDED | $85,370 | $295,760 |
$18,230
524,100
kWh
|
$13,110
-
kW-mo/yr
|
$50,130
-
MMBtu
|
$1,120
-
Tgal
|
$900 | $960 |
$920
-
Tgal
|
||
TOTAL IMPLEMENTED | $25,370 | $16,780 |
$13,850
398,200
kWh
|
$7,450
-
kW-mo/yr
|
$850
-
MMBtu
|
$1,120
-
Tgal
|
$660 | $520 |
$920
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs