Assessment Year | 1996 |
---|---|
Principal Product | industrial wire products |
NAICS |
n/a
|
SIC | 3496: Miscellaneous Fabricated Wire Products |
Sales Range | $10 M to 50M |
# of Employees | 75 |
Plant Area |
72,000
ft2
|
Annual Production | 31,000
ton
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $81,175 | 4,018,464 |
kWh
|
$0.020 |
Electricity Demand | $34,300 | 9,876 |
kW-mo/yr
|
$3.47 |
Natural Gas | $51,573 | 18,306 |
MMBtu
|
$2.82 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $12,530 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,599 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $1,992 | $6,660 | - | - | - | $1,992 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,837 | $2,776 |
$1,546
81,477
kWh
|
$291
-
kW-mo/yr
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,302 | $5,112 |
$1,011
53,341
kWh
|
$291
-
kW-mo/yr
|
- | - | |
04 | 2.7135: Install occupancy sensors | $1,939 | $1,074 |
$1,618
85,287
kWh
|
$321
-
kW-mo/yr
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,052 | $100 |
$810
42,790
kWh
|
$242
-
kW-mo/yr
|
- | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $347 | $114 |
$295
15,533
kWh
|
$52
-
kW-mo/yr
|
- | - | |
07 | 2.4314: Use synthetic lubricant | $370 | $915 |
$285
14,947
kWh
|
$55
-
kW-mo/yr
|
$30
-
lb
|
- | |
08 | 2.4133: Use most efficient type of electric motors | $428 | $1,082 |
$352
18,464
kWh
|
$76
-
kW-mo/yr
|
- | - | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,263 | $3,412 |
$2,751
144,783
kWh
|
$512
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $12,530 | $21,245 |
$8,668
456,622
kWh
|
$1,840
-
kW-mo/yr
|
$30
-
lb
|
$1,992 | ||
TOTAL IMPLEMENTED | $8,599 | $13,511 |
$7,050
371,335
kWh
|
$1,519
-
kW-mo/yr
|
$30
-
lb
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs