Assessment Year | 1996 |
---|---|
Principal Product | balls for bearings |
NAICS |
n/a
|
SIC | 3562: Ball and Roller Bearings |
Sales Range | $10 M to 50M |
# of Employees | 87 |
Plant Area |
88,800
ft2
|
Annual Production | 240
ton
|
Production Hrs. Annual | 8,232
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $255,315 | 8,238,863 |
kWh
|
$0.031 |
Electricity Demand | $87,507 | 5,144 |
kW-mo/yr
|
$17.01 |
Natural Gas | $25,244 | 9,469 |
MMBtu
|
$2.67 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,993 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,810 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $11,023 | $3,165 |
$8,560
285,463
kWh
|
$2,463
-
kW-mo/yr
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $2,336 | $2,516 |
$1,644
43,083
kWh
|
$692
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,308 | $3,238 |
$3,556
93,494
kWh
|
$752
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,073 | $6,236 |
$1,500
50,117
kWh
|
$573
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $2,048 | $2,432 |
$1,442
48,066
kWh
|
$606
-
kW-mo/yr
|
- | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,474 | $670 |
$1,161
38,687
kWh
|
$313
-
kW-mo/yr
|
- | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,809 | $5,572 |
$1,423
47,479
kWh
|
$386
-
kW-mo/yr
|
- | |
08 | 2.2511: Insulate bare equipment | $922 | $536 |
$1,180
39,273
kWh
|
- |
$(-258.0)
-
MMBtu
|
|
09 | 3.5315: Lease / purchase baler; sell cardboard to recycler | - | - | - | - | - | |
TOTAL RECOMMENDED | $25,993 | $24,365 |
$20,466
645,662
kWh
|
$5,785
-
kW-mo/yr
|
$(-258.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $3,810 | $3,186 |
$2,805
81,770
kWh
|
$1,005
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs