| Assessment Year | 1995 |
|---|---|
| Principal Product | wallboard |
| NAICS |
n/a
|
| SIC | 3275: Gypsum Products |
| Sales Range | $50 M to 100M |
| # of Employees | 204 |
| Plant Area |
125,000
ft2
|
| Annual Production | 550,000
thousand feet
|
| Production Hrs. Annual | 8,568
hrs
|
| Location (State) | Iowa |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $962,800 | 35,548,945 |
kWh
|
$0.027 |
| Natural Gas | $4,366,418 | 1,494,549 |
MMBtu
|
$2.92 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $149,987 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $139,480 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2443: Re-use or recycle hot or cold process exhaust air | $109,407 | $175,000 | - |
$109,407
-
MMBtu
|
|
| 02 | 2.4133: Use most efficient type of electric motors | $30,073 | $11,336 |
$30,073
1,110,199
kWh
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,085 | $20,342 |
$4,085
150,938
kWh
|
- | |
| 04 | 2.7135: Install occupancy sensors | $745 | $1,155 |
$745
27,550
kWh
|
- | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,013 | $100 |
$4,013
148,007
kWh
|
- | |
| 06 | 2.6212: Turn off equipment during breaks, reduce operating time | $341 | $25 |
$341
12,603
kWh
|
- | |
| 07 | 2.7261: Install timers and/or thermostats | $1,323 | $266 |
$903
33,411
kWh
|
$420
-
MMBtu
|
|
| TOTAL RECOMMENDED | $149,987 | $208,224 |
$40,160
1,482,708
kWh
|
$109,827
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $139,480 | $186,336 |
$30,073
1,110,199
kWh
|
$109,407
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs