Assessment Year | 1992 |
---|---|
Principal Product | DIES AND STAMPINGS |
NAICS |
n/a
|
SIC | 3544: Special Dies and Tools, Die Sets, Jigs and Fixtures, and Industrial Molds |
Sales Range | $5 M to 10M |
# of Employees | 126 |
Plant Area |
n/a
|
Annual Production | 500,000
lb
|
Production Hrs. Annual | 5,538
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $66,145 | 1,598,476 |
kWh
|
$0.041 |
Natural Gas | $16,201 | 3,789 |
MMBtu
|
$4.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,090 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,216 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7492: Use proper thickness of insulation on building envelope | $9,403 | $29,569 | - |
$9,403
-
MMBtu
|
- | |
02 | 2.7314: Reduce ventilation air | $3,352 | - |
$1,007
24,326
kWh
|
$2,345
-
MMBtu
|
- | |
03 | 2.7231: Use radiant heater for spot heating | $4,443 | $12,690 | - |
$4,443
-
MMBtu
|
- | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $4,618 | $630 |
$4,553
109,906
kWh
|
- | $65 | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,259 | $214 |
$2,553
61,547
kWh
|
- | $(-294.0) | |
06 | 2.6232: Install set-back timers | $1,425 | $2,304 |
$1,425
34,291
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $169 | $300 |
$169
4,103
kWh
|
- | - | |
08 | 2.4133: Use most efficient type of electric motors | $357 | $4,230 |
$357
8,499
kWh
|
- | - | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $383 | $200 |
$383
9,379
kWh
|
- | - | |
10 | 2.8121: Apply for tax-free status for energy purchases | $2,681 | $250 |
$2,681
-
kWh
|
- | - | |
TOTAL RECOMMENDED | $29,090 | $50,387 |
$13,128
252,051
kWh
|
$16,191
-
MMBtu
|
$(-229.0) | ||
TOTAL IMPLEMENTED | $11,216 | $17,370 |
$4,428
42,204
kWh
|
$6,788
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs