Assessment Year | 1999 |
---|---|
Principal Product | Composite Plastics |
NAICS |
n/a
|
SIC | 3083: Laminated Plastics Plate, Sheet, and Profile Shapes |
Sales Range | $5 M to 10M |
# of Employees | 60 |
Plant Area |
64,000
ft2
|
Annual Production | 45
ton
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $87,863 | 1,047,773 |
kWh
|
$0.084 |
Electricity Demand | $37,730 | 3,439 |
kW-mo/yr
|
$10.97 |
Electricity Fees | $10,649 | - |
|
- |
Natural Gas | $50,157 | 9,905 |
MMBtu
|
$5.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $19,159 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,287 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,758 | $16,993 |
$3,692
43,962
kWh
|
$2,066
-
kW-mo/yr
|
- | - | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $785 | $1,000 |
$506
6,155
kWh
|
$279
-
kW-mo/yr
|
- | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,524 | $360 |
$1,524
16,706
kWh
|
- | - | - | - | |
04 | 2.7496: Install partitions to reduce size of conditioned space | $395 | $400 | - | - |
$395
-
MMBtu
|
- | - | |
05 | 2.7233: Use properly designed and sized hvac equipment | $825 | $2,000 | - | - |
$825
-
MMBtu
|
- | - | |
06 | 4.611: Begin a practice of predictive / preventative maintenance | $1,000 | $300 | - | - | - | - | $1,000 | |
07 | 3.5212: Regrind, reuse, or sell scrap plastic parts | $1,872 | $3,500 | - | - | - |
$1,872
-
lb
|
- | |
08 | 4.123: Reduce defects by reducing product tipping | $2,000 | $10,000 | - | - | - | - | $2,000 | |
09 | 4.123: Reduce defects by reducing product tipping | $5,000 | $3,000 | - | - | - | - | $5,000 | |
TOTAL RECOMMENDED | $19,159 | $37,553 |
$5,722
66,823
kWh
|
$2,345
-
kW-mo/yr
|
$1,220
-
MMBtu
|
$1,872
-
lb
|
$8,000 | ||
TOTAL IMPLEMENTED | $10,287 | $21,053 |
$5,722
66,823
kWh
|
$2,345
-
kW-mo/yr
|
$1,220
-
MMBtu
|
- | $1,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs