Assessment Year 1996
Principal Product Cosmetics
NAICS
n/a
SIC 2844: Perfumes, Cosmetics, and Other Toilet Preparations
Sales Range $100
M
to 500
M
# of Employees 350
Plant Area 205,000
ft2
Annual Production 120,000,000
pieces
Production Hrs. Annual 6,400
hrs
Location (State) New Jersey

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $742,725 9,453,986
kWh
Electricity Demand $201,909 22,643
kW-mo/yr
Electricity Fees $(-164,312.0) -
Natural Gas $115,488 30,897
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $9,923 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $8,523

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings
01 2.4221: Install compressor air intakes in coolest locations $3,210 $1,200 $2,650
33,705
kWh
$560
-
kW-mo/yr
- -
02 2.4133: Use most efficient type of electric motors $5,138 $9,130 $4,239
53,927
kWh
$899
-
kW-mo/yr
- -
03 2.2135: Repair and eliminate steam leaks $175 $100 - - $175
-
MMBtu
-
04 3.4114: Replace city water with recycled water via cooling tower $1,400 $5,000 - - - $1,400
-
Tgal
TOTAL RECOMMENDED $9,923 $15,430 $6,889
87,632
kWh
$1,459
-
kW-mo/yr
$175
-
MMBtu
$1,400
-
Tgal
TOTAL IMPLEMENTED $8,523 $10,430 $6,889
87,632
kWh
$1,459
-
kW-mo/yr
$175
-
MMBtu
-
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs