Assessment Year | 1994 |
---|---|
Principal Product | Bonded Fiber Products |
NAICS |
n/a
|
SIC | 2297: Non-woven Fabrics |
Sales Range | $10 M to 50M |
# of Employees | 125 |
Plant Area |
265,000
ft2
|
Annual Production | 300,000
thousand feet
|
Production Hrs. Annual | 3,432
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $613,690 | 6,360,199 |
kWh
|
$0.096 |
Fuel Oil #6 | $236,772 | 71,792 |
MMBtu
|
$3.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $9,892 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Fuel Oil #6 Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,262 | $4,494 |
$4,262
43,962
kWh
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,141 | $3,201 |
$1,141
11,723
kWh
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $1,251 | $4,495 |
$1,251
12,896
kWh
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $2,327 | $1,200 |
$2,327
24,033
kWh
|
- | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $305 | $80 |
$305
3,224
kWh
|
- | |
06 | 2.2511: Insulate bare equipment | $467 | $472 | - |
$467
-
MMBtu
|
|
07 | 2.2136: Install / repair insulation on steam lines | $139 | $375 | - |
$139
-
MMBtu
|
|
TOTAL RECOMMENDED | $9,892 | $14,317 |
$9,286
95,838
kWh
|
$606
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Fuel Oil #6 Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs