| Assessment Year | 2026 |
|---|---|
| Principal Product | Demountable Interior Walls |
| NAICS | 332321: Metal Window and Door Manufacturing |
| SIC | 3442: Metal Doors, Sash, Frames, Molding, and Trim Manufacturing |
| Sales Range | $50 M to 100M |
| # of Employees | 198 |
| Plant Area |
82,000
ft2
|
| Annual Production | 499,549
pieces
|
| Production Hrs. Annual | 6,300
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $191,021 | 1,369,120 |
kWh
|
$0.14 |
| Natural Gas | $24,677 | 3,580 |
MMBtu
|
$6.89 |
| Other Gas | $1,728 | 1 |
MMBtu
|
$1,727.53 |
| TOTAL YEARLY COSTS | $217,426 | |||
| RECOMMENDED SAVINGS* | $130,803 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Other Gas Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $34,896 | $1,850 |
$37,796
269,971
kWh
|
- | - | $(-2,900.0) | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,071 | $400 |
$3,071
21,939
kWh
|
- | - | - | |
| 03 | 2.8121: Apply for tax-free status for energy purchases | $1,463 | $200 | - | - |
$1,463
-
MMBtu
|
- | |
| 04 | 2.4239: Eliminate or reduce compressed air usage | $10,214 | $2,000 |
$10,214
72,965
kWh
|
- | - | - | |
| 05 | 2.2511: Insulate bare equipment | $2,548 | $640 | - |
$2,548
-
MMBtu
|
- | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,778 | $2,389 |
$2,778
19,845
kWh
|
- | - | - | |
| 07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $7,162 | $8,061 |
$3,242
23,154
kWh
|
$3,920
-
MMBtu
|
- | - | |
| 08 | 2.6212: Turn off equipment during breaks, reduce operating time | $515 | $680 |
$515
3,679
kWh
|
- | - | - | |
| 09 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $3,355 | $8,200 |
$3,355
23,968
kWh
|
- | - | - | |
| 10 | 2.9114: Use solar heat to make electricty | $64,801 | $290,462 |
$64,801
464,455
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $130,803 | $314,882 |
$125,772
899,976
kWh
|
$6,468
-
MMBtu
|
$1,463
-
MMBtu
|
$(-2,900.0) | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Other Gas Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs