| Assessment Year | 2021 |
|---|---|
| Principal Product | Custom Metal Powder Coated Products |
| NAICS | 332812: Metal Coating, Engraving (except Jewelry and Silverware), and Allied Services to Manufacturers |
| SIC | 3479: Coating, Engraving, and Allied Services, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 85 |
| Plant Area |
50,000
ft2
|
| Annual Production | 6,060,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $139,171 | 1,434,720 |
kWh
|
$0.097 |
| Natural Gas | $144,560 | 45,399 |
MMBtu
|
$3.18 |
| TOTAL YEARLY COSTS | $283,731 | |||
| RECOMMENDED SAVINGS* | $41,560 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $12,318 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,577 | $1,850 |
$8,477
87,394
kWh
|
$(-2,900.0) | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,031 | $400 |
$1,031
10,630
kWh
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,911 | $2,747 |
$4,911
50,633
kWh
|
- | |
| 04 | 2.7261: Install timers and/or thermostats | $326 | $225 |
$326
3,364
kWh
|
- | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $7,985 | $8,432 |
$7,985
82,322
kWh
|
- | |
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $472 | $1,123 |
$472
4,864
kWh
|
- | |
| 07 | 2.7135: Install occupancy sensors | $1,866 | $5,680 |
$1,866
19,234
kWh
|
- | |
| 08 | 2.9114: Use solar heat to make electricty | $19,391 | $226,091 |
$19,391
199,899
kWh
|
- | |
| TOTAL RECOMMENDED | $41,560 | $246,549 |
$44,460
458,341
kWh
|
$(-2,900.0) | ||
| TOTAL IMPLEMENTED | $12,318 | $6,346 |
$15,218
156,886
kWh
|
$(-2,900.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs