| Assessment Year | 2008 |
|---|---|
| Principal Product | Pork Rinds |
| NAICS | 311919: Other Snack Food Manufacturing |
| SIC | 2096: Potato Chips, Corn Chips, and Similar Snacks |
| Sales Range | $10 M to 50M |
| # of Employees | 56 |
| Plant Area |
38,000
ft2
|
| Annual Production | 7,000,000
lb
|
| Production Hrs. Annual | 4,117
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $29,360 | 793,800 |
kWh
|
$0.037 |
| Electricity Demand | $26,372 | 2,074 |
kW-mo/yr
|
$12.72 |
| Electricity Fees | $8,647 | - |
|
- |
| Natural Gas | $68,360 | 5,511 |
MMBtu
|
$12.40 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $41,615 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $7,944 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,022 | $9,780 |
$4,041
105,514
kWh
|
$1,981
-
kW-mo/yr
|
- | |
| 02 | 2.7135: Install occupancy sensors | $1,127 | $1,120 |
$1,127
29,434
kWh
|
- | - | |
| 03 | 2.2424: Use heat in flue gases to preheat products or materials | $10,291 | $19,600 | - | - |
$10,291
-
MMBtu
|
|
| 04 | 2.2437: Recover waste heat from equipment | $19,920 | $17,000 | - | - |
$19,920
-
MMBtu
|
|
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $795 | $500 |
$403
10,516
kWh
|
$392
-
kW-mo/yr
|
- | |
| 06 | 2.7241: Install outside air damper / economizer on hvac unit | $834 | $2,100 |
$834
21,775
kWh
|
- | - | |
| 07 | 2.2437: Recover waste heat from equipment | $1,537 | $2,500 |
$(-238.0)
(-6,216)
kWh
|
- |
$1,775
-
MMBtu
|
|
| 08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,089 | $1,350 |
$1,089
28,427
kWh
|
- | - | |
| TOTAL RECOMMENDED | $41,615 | $53,950 |
$7,256
189,450
kWh
|
$2,373
-
kW-mo/yr
|
$31,986
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $7,944 | $11,400 |
$5,571
145,464
kWh
|
$2,373
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs