Assessment Year | 2007 |
---|---|
Principal Product | Shelled Peanuts |
NAICS | 311911: Roasted Nuts and Peanut Butter Manufacturing |
SIC | 2068: Salted and Roasted Nuts and Seeds |
Sales Range | $5 M to 10M |
# of Employees | 35 |
Plant Area |
30,000
ft2
|
Annual Production | 14,000
ton
|
Production Hrs. Annual | 4,368
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $138,734 | 2,416,960 |
kWh
|
$0.057 |
Electricity Demand | $50,189 | 6,819 |
kW-mo/yr
|
$7.36 |
Electricity Fees | $12,796 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $24,238 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,304 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,121 | $1,250 |
$832
13,560
kWh
|
$289
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $160 | $132 |
$118
1,922
kWh
|
$42
-
kW-mo/yr
|
- | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,424 | $1,967 |
$1,424
23,184
kWh
|
- | - | |
04 | 2.4314: Use synthetic lubricant | $4,306 | - |
$4,306
70,106
kWh
|
- | - | |
05 | 2.4321: Upgrade obsolete equipment | $5,731 | - |
$3,503
57,031
kWh
|
$2,228
-
kW-mo/yr
|
- | |
06 | 2.4239: Eliminate or reduce compressed air usage | $1,623 | $1,000 |
$952
15,506
kWh
|
$671
-
kW-mo/yr
|
- | |
07 | 2.4133: Use most efficient type of electric motors | $5,453 | $9,501 |
$4,033
65,656
kWh
|
$1,420
-
kW-mo/yr
|
- | |
08 | 2.6223: Schedule use of elevators to conserve energy | $2,640 | $15,000 | - | - | $2,640 | |
09 | 2.6242: Minimize operation of equipment maintained in standby condition | $1,780 | $15,000 |
$1,780
28,980
kWh
|
- | - | |
TOTAL RECOMMENDED | $24,238 | $43,850 |
$16,948
275,945
kWh
|
$4,650
-
kW-mo/yr
|
$2,640 | ||
TOTAL IMPLEMENTED | $12,304 | $12,718 |
$10,595
172,506
kWh
|
$1,709
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs