| Assessment Year | 2005 |
|---|---|
| Principal Product | Air Conditioners |
| NAICS | 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen |
| SIC | 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment |
| Sales Range | $50 M to 100M |
| # of Employees | 600 |
| Plant Area |
700,000
ft2
|
| Annual Production | 250,000
pieces
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,022,787 | 18,440,471 |
kWh
|
$0.055 |
| Natural Gas | $506,970 | 69,910 |
MMBtu
|
$7.25 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $141,169 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $54,884 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7124: Make a practice of turning off lights when not needed | $15,771 | - |
$15,771
406,477
kWh
|
- | - | - | |
| 02 | 2.4314: Use synthetic lubricant | $7,490 | - |
$7,490
193,100
kWh
|
- | - | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $36,600 | $10,000 |
$36,600
942,000
kWh
|
- | - | - | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,513 | $1,475 |
$2,513
64,770
kWh
|
- | - | - | |
| 05 | 2.6218: Turn off equipment when not in use | $3,160 | $2,180 |
$3,160
81,500
kWh
|
- | - | - | |
| 06 | 2.1133: Adjust burners for efficient operation | $8,596 | - | - | - |
$11,746
-
MMBtu
|
$(-3,150.0) | |
| 07 | 2.4133: Use most efficient type of electric motors | $8,741 | $10,484 |
$4,906
174,000
kWh
|
$3,835
-
kW-mo/yr
|
- | - | |
| 08 | 2.4239: Eliminate or reduce compressed air usage | $305 | $700 |
$305
7,827
kWh
|
- | - | - | |
| 09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,388 | $35,680 |
$6,504
230,655
kWh
|
$4,884
-
kW-mo/yr
|
- | - | |
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,948 | $39,765 |
$7,417
263,010
kWh
|
$5,531
-
kW-mo/yr
|
- | - | |
| 11 | 2.4224: Upgrade controls on compressors | $10,500 | $35,000 |
$10,500
270,725
kWh
|
- | - | - | |
| 12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $23,157 | $102,196 |
$13,265
470,400
kWh
|
$9,892
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $141,169 | $237,480 |
$108,431
3,104,464
kWh
|
$24,142
-
kW-mo/yr
|
$11,746
-
MMBtu
|
$(-3,150.0) | ||
| TOTAL IMPLEMENTED | $54,884 | $11,475 |
$54,884
1,413,247
kWh
|
- | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs