| Assessment Year | 2001 |
|---|---|
| Principal Product | Tire Retread |
| NAICS |
n/a
|
| SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 200 |
| Plant Area |
126,000
ft2
|
| Annual Production | 700,000
pieces
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $453,167 | 18,602,914 |
kWh
|
$0.024 |
| Electricity Demand | $403,241 | 35,372 |
kW-mo/yr
|
$11.40 |
| Electricity Fees | $83,547 | - |
|
- |
| Natural Gas | $637,755 | 74,993 |
MMBtu
|
$8.50 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $239,162 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $14,000 | - | n/a | - | - | $20,000 | $(-6,000.0) | - |
| 02 | 2.8112: Combine utility meters | $2,360 | - | n/a | - | - | - | - | $2,360 |
| 03 | 2.4235: Remove or close off unneeded compressed air lines | $645 | - | n/a |
$610
25,032
kWh
|
- | $35 | - | - |
| 04 | 2.4224: Upgrade controls on compressors | $1,625 | $7,000 | n/a |
$1,536
63,040
kWh
|
- | $89 | - | - |
| 05 | 2.1114: Limit and control secondary combustion air in furnace | $35,705 | $3,500 | n/a | - | - | $35,705 | - | - |
| 06 | 4.445: Install equipment to move product | $99,000 | $80,000 | n/a | - | - | - | $99,000 | - |
| 07 | 2.2426: Use waste heat from flue gases to heat space conditioning air | $12,400 | $30,000 | n/a | - | - | $12,400 | - | - |
| 08 | 3.8131: Use water-based adhesives | $73,300 | $20,000 | n/a |
$1,604
65,856
kWh
|
$1,532
-
kW-mo/yr
|
$70,164 | - | - |
| 09 | 2.8112: Combine utility meters | $127 | - | n/a | - | - | - | - | $127 |
| TOTAL RECOMMENDED | $239,162 | $140,500 |
$3,750
153,928
kWh
|
$1,532
-
kW-mo/yr
|
$138,393 | $93,000 | $2,487 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs