Assessment Year | 1996 |
---|---|
Principal Product | Salad Dressings & Sauces |
NAICS |
n/a
|
SIC | 2035: Pickled Fruits and Vegetables, Vegetable Sauces and Seasonings, and Salad Dressings |
Sales Range | $50 M to 100M |
# of Employees | 240 |
Plant Area |
100,000
ft2
|
Annual Production | 60,000,000
lb
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $292,846 | 7,598,476 |
kWh
|
$0.039 |
Electricity Demand | $114,589 | 9,080 |
kW-mo/yr
|
$12.62 |
Electricity Fees | $402 | - |
|
- |
Natural Gas | $72,286 | 14,458 |
MMBtu
|
$5.00 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $98,466 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $76,156 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.8113: Purchase gas directly from a contract gas supplier | $21,137 | $50,000 | - | - | - | - | $21,137 | |
02 | 2.1231: Establish burner maintenance schedule for boilers | $2,045 | $1,000 | - | - |
$2,045
-
MMBtu
|
- | - | |
03 | 2.2121: Increase amount of condensate returned | $27,914 | $12,000 |
$8,529
341,149
kWh
|
$12,282
-
kW-mo/yr
|
$4,260
-
MMBtu
|
$2,843
-
Tgal
|
- | |
04 | 2.6218: Turn off equipment when not in use | $3,970 | $500 | - | - |
$3,970
-
MMBtu
|
- | - | |
05 | 2.3191: Use demand controller or load shedder | $21,460 | - | - | - | - | - | $21,460 | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $21,090 | $34,520 |
$8,045
321,805
kWh
|
$13,045
-
kW-mo/yr
|
- | - | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $850 | $2,100 |
$467
18,757
kWh
|
$383
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $98,466 | $100,120 |
$17,041
681,711
kWh
|
$25,710
-
kW-mo/yr
|
$10,275
-
MMBtu
|
$2,843
-
Tgal
|
$42,597 | ||
TOTAL IMPLEMENTED | $76,156 | $98,020 |
$16,574
662,954
kWh
|
$25,327
-
kW-mo/yr
|
$10,275
-
MMBtu
|
$2,843
-
Tgal
|
$21,137 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs