| Assessment Year | 1994 |
|---|---|
| Principal Product | Vegetable Oil |
| NAICS |
n/a
|
| SIC | 2079: Shortening, Table Oils, Margarine, and Other Edible Fats and Oils, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 28 |
| Plant Area |
10,000
ft2
|
| Annual Production | 55,773,983
lb
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $98,121 | 1,900,352 |
kWh
|
$0.052 |
| Natural Gas | $220,613 | 60,907 |
MMBtu
|
$3.62 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $36,053 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $18,773 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2414: Use waste heat from hot flue gases to preheat | $14,750 | $14,450 | - |
$14,750
-
MMBtu
|
|
| 02 | 2.2121: Increase amount of condensate returned | $10,138 | $3,400 | - |
$10,138
-
MMBtu
|
|
| 03 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $2,530 | $7,185 | - |
$2,530
-
MMBtu
|
|
| 04 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $5,880 | $8,250 | - |
$5,880
-
MMBtu
|
|
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,940 | $5,000 |
$1,940
37,515
kWh
|
- | |
| 06 | 2.4227: Use compressor air filters | $815 | $750 |
$815
15,826
kWh
|
- | |
| TOTAL RECOMMENDED | $36,053 | $39,035 |
$2,755
53,341
kWh
|
$33,298
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $18,773 | $17,400 |
$2,755
53,341
kWh
|
$16,018
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs