| Assessment Year | 1994 |
|---|---|
| Principal Product | Plastic Film Bags |
| NAICS |
n/a
|
| SIC | 2673: Plastics, Foil, and Coated Paper Bags |
| Sales Range | $100 M to 500M |
| # of Employees | 724 |
| Plant Area |
495,000
ft2
|
| Annual Production | 100,000,000
lb
|
| Production Hrs. Annual | 8,232
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $3,060,354 | 67,036,636 |
kWh
|
$0.046 |
| Natural Gas | $82,274 | 29,966 |
MMBtu
|
$2.75 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $402,540 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $30,170 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $22,230 | $2,500 |
$22,230
486,518
kWh
|
- | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $7,850 | $3,000 |
$7,850
171,747
kWh
|
- | |
| 03 | 2.4314: Use synthetic lubricant | $14,510 | - |
$14,510
317,409
kWh
|
- | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $8,870 | $3,250 |
$8,870
194,021
kWh
|
- | |
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $90,740 | $160,000 |
$90,740
1,985,932
kWh
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,570 | $18,880 |
$5,570
121,923
kWh
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,370 | $4,860 |
$2,370
51,876
kWh
|
- | |
| 08 | 2.7229: Air condition only space necessary | $22,300 | $1,890 |
$22,300
1,070,633
kWh
|
- | |
| 09 | 2.4133: Use most efficient type of electric motors | $228,100 | $770,000 |
$68,100
1,490,328
kWh
|
$160,000 | |
| TOTAL RECOMMENDED | $402,540 | $964,380 |
$242,540
5,890,387
kWh
|
$160,000 | ||
| TOTAL IMPLEMENTED | $30,170 | $26,240 |
$30,170
660,317
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs