ITAC Assessment: GT0538
ITAC logo
ITAC Assessment: GT0538
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1994
Principal Product Plastic Film Bags
NAICS
n/a
SIC 2673: Plastics, Foil, and Coated Paper Bags
Sales Range $100
M
to 500
M
# of Employees 724
Plant Area 495,000
ft2
Annual Production 100,000,000
lb
Production Hrs. Annual 8,232
hrs
Location (State) Georgia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $3,060,354 67,036,636
kWh
Natural Gas $82,274 29,966
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $402,540 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $30,170

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Personnel Changes Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $22,230 $2,500 $22,230
486,518
kWh
-
02 2.4221: Install compressor air intakes in coolest locations $7,850 $3,000 $7,850
171,747
kWh
-
03 2.4314: Use synthetic lubricant $14,510 - $14,510
317,409
kWh
-
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $8,870 $3,250 $8,870
194,021
kWh
-
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $90,740 $160,000 $90,740
1,985,932
kWh
-
06 2.7142: Utilize higher efficiency lamps and/or ballasts $5,570 $18,880 $5,570
121,923
kWh
-
07 2.7142: Utilize higher efficiency lamps and/or ballasts $2,370 $4,860 $2,370
51,876
kWh
-
08 2.7229: Air condition only space necessary $22,300 $1,890 $22,300
1,070,633
kWh
-
09 2.4133: Use most efficient type of electric motors $228,100 $770,000 $68,100
1,490,328
kWh
$160,000
TOTAL RECOMMENDED $402,540 $964,380 $242,540
5,890,387
kWh
$160,000
TOTAL IMPLEMENTED $30,170 $26,240 $30,170
660,317
kWh
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs