| Assessment Year | 1993 |
|---|---|
| Principal Product | Synthetic Yarn |
| NAICS |
n/a
|
| SIC | 2221: Broadwoven Fabric Mills, Manmade Fiber and Silk |
| Sales Range | $10 M to 50M |
| # of Employees | 276 |
| Plant Area |
180,000
ft2
|
| Annual Production | 20,400,000
lb
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $663,573 | 12,633,060 |
kWh
|
$0.053 |
| Natural Gas | $216,188 | 75,197 |
MMBtu
|
$2.87 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $71,820 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $57,300 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,090 | $450 | - |
$1,090
-
MMBtu
|
|
| 02 | 2.2414: Use waste heat from hot flue gases to preheat | $7,880 | $11,800 | - |
$7,880
-
MMBtu
|
|
| 03 | 2.2414: Use waste heat from hot flue gases to preheat | $2,620 | $7,280 | - |
$2,620
-
MMBtu
|
|
| 04 | 2.4133: Use most efficient type of electric motors | $26,920 | $103,820 |
$26,920
501,172
kWh
|
- | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $12,320 | - |
$12,320
223,623
kWh
|
- | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $710 | $700 |
$710
13,482
kWh
|
- | |
| 07 | 2.7135: Install occupancy sensors | $1,450 | $630 |
$1,450
27,843
kWh
|
- | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,990 | $58,000 |
$15,990
304,807
kWh
|
- | |
| 09 | 2.7122: Disconnect ballasts | $980 | $1,200 |
$980
18,757
kWh
|
- | |
| 10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,860 | $5,700 |
$1,860
35,463
kWh
|
- | |
| TOTAL RECOMMENDED | $71,820 | $189,580 |
$60,230
1,125,147
kWh
|
$11,590
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $57,300 | $163,470 |
$56,210
1,048,359
kWh
|
$1,090
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs