Assessment Year | 1992 |
---|---|
Principal Product | DYED CARPETS |
NAICS |
n/a
|
SIC | 2273: Carpets and Rugs |
Sales Range | $100 M to 500M |
# of Employees | 130 |
Plant Area |
n/a
|
Annual Production | 108,000
thousand feet
|
Production Hrs. Annual | 5,400
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $388,700 | 10,224,795 |
kWh
|
$0.038 |
Natural Gas | $506,949 | 141,733 |
MMBtu
|
$3.58 |
Fuel Oil #6 | $395,256 | 183,716 |
MMBtu
|
$2.15 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $93,238 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #6 Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $46,283 | $1,000 | - |
$26,573
-
MMBtu
|
$20,710
-
MMBtu
|
$(-1,000.0) | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $5,240 | $10,000 | - |
$2,945
-
MMBtu
|
$2,295
-
MMBtu
|
- | |
03 | 2.2414: Use waste heat from hot flue gases to preheat | $22,360 | $33,000 | - |
$12,566
-
MMBtu
|
$9,794
-
MMBtu
|
- | |
04 | 2.2136: Install / repair insulation on steam lines | $565 | $1,160 | - |
$318
-
MMBtu
|
$247
-
MMBtu
|
- | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $250 | - |
$250
6,448
kWh
|
- | - | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $14,501 | $81,480 |
$14,501
381,594
kWh
|
- | - | - | |
07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $2,120 | $4,800 | - |
$2,120
-
MMBtu
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $562 | $10,850 |
$562
14,654
kWh
|
- | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $677 | $4,920 |
$778
20,516
kWh
|
- | - | $(-101.0) | |
10 | 2.7111: Reduce illumination to minimum necessary levels | $680 | $660 |
$680
17,878
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $93,238 | $147,870 |
$16,771
441,090
kWh
|
$44,522
-
MMBtu
|
$33,046
-
MMBtu
|
$(-1,101.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #6 Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs