Assessment Year | 1997 |
---|---|
Principal Product | Computer Chips and Processors |
NAICS |
n/a
|
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 650 |
Plant Area |
250,000
ft2
|
Annual Production | 71,550
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Minnesota |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $788,457 | 26,771,689 |
kWh
|
$0.029 |
Electricity Demand | $370,595 | 49,212 |
kW-mo/yr
|
$7.53 |
Electricity Fees | $14,649 | - |
|
- |
Natural Gas | $237,922 | 70,070 |
MMBtu
|
$3.40 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $62,602 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $47,761 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $6,948 | $3,808 | - | - | $6,948 | - | - | - | - | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $960 | - | - | - | - |
$960
-
MMBtu
|
- | - | - | |
03 | 2.2511: Insulate bare equipment | $1,477 | $2,969 | - | - | - |
$1,477
-
MMBtu
|
- | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $1,631 | $450 |
$1,387
47,773
kWh
|
$244
-
kW-mo/yr
|
- | - | - | - | - | |
05 | 3.8142: Distill contaminated solvents for reuse | $14,841 | $17,500 | - | - | - | - | - |
$14,841
-
gal
|
- | |
06 | 3.4116: Meter recycled water (to reduce sewer charges) | $17,888 | $10,590 | - | - | - | - |
$17,888
-
Tgal
|
- | - | |
07 | 2.8123: Pay utility bills on time | $2,645 | - | - | - | - | - | - | - | $2,645 | |
08 | 2.8121: Apply for tax-free status for energy purchases | $16,212 | $450 | - | - | - | - | - | - | $16,212 | |
TOTAL RECOMMENDED | $62,602 | $35,767 |
$1,387
47,773
kWh
|
$244
-
kW-mo/yr
|
$6,948 |
$2,437
-
MMBtu
|
$17,888
-
Tgal
|
$14,841
-
gal
|
$18,857 | ||
TOTAL IMPLEMENTED | $47,761 | $18,267 |
$1,387
47,773
kWh
|
$244
-
kW-mo/yr
|
$6,948 |
$2,437
-
MMBtu
|
$17,888
-
Tgal
|
- | $18,857 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs