Assessment Year | 1996 |
---|---|
Principal Product | Pasta |
NAICS |
n/a
|
SIC | 2098: Macaroni, Spaghetti, Vermicelli, and Noodles |
Sales Range | $10 M to 50M |
# of Employees | 225 |
Plant Area |
175,869
ft2
|
Annual Production | 155,000,000
lb
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Minnesota |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $387,516 | 13,623,095 |
kWh
|
$0.028 |
Electricity Demand | $185,761 | 24,708 |
kW-mo/yr
|
$7.52 |
Electricity Fees | $20,583 | - |
|
- |
Natural Gas | $214,724 | 89,531 |
MMBtu
|
$2.40 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $21,853 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,371 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $4,015 | $67,277 |
$2,849
99,941
kWh
|
$1,166
-
kW-mo/yr
|
- | - | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $1,927 | $675 |
$1,647
57,737
kWh
|
$280
-
kW-mo/yr
|
- | - | - | |
03 | 2.1213: Direct warmest air to combustion intake | $1,689 | $1,110 | - | - |
$1,689
-
MMBtu
|
- | - | |
04 | 3.4156: Use flow control valves on equipment to optimize water use | $5,139 | $10,000 | - | - | - |
$3,173
-
Tgal
|
$1,966
-
Tgal
|
|
05 | 2.2511: Insulate bare equipment | $3,328 | $3,572 | - | - |
$3,328
-
MMBtu
|
- | - | |
06 | 3.4151: Minimize water usage | $5,755 | $3,000 | - | - | - |
$3,554
-
Tgal
|
$2,201
-
Tgal
|
|
TOTAL RECOMMENDED | $21,853 | $85,634 |
$4,496
157,678
kWh
|
$1,446
-
kW-mo/yr
|
$5,017
-
MMBtu
|
$6,727
-
Tgal
|
$4,167
-
Tgal
|
||
TOTAL IMPLEMENTED | $9,371 | $4,785 |
$1,647
57,737
kWh
|
$280
-
kW-mo/yr
|
$1,689
-
MMBtu
|
$3,554
-
Tgal
|
$2,201
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs