Assessment Year | 2023 |
---|---|
Principal Product | Malt beverages |
NAICS | 312120: Breweries |
SIC | 2082: Malt Beverages |
Sales Range | $50 M to 100M |
# of Employees | 96 |
Plant Area |
177,000
ft2
|
Annual Production | 8,960
Tgal
|
Production Hrs. Annual | 7,072
hrs
|
Location (State) | Delaware |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $751,293 | 8,254,091 |
kWh
|
$0.091 |
Electricity Demand | $113,153 | 21,861 |
kW-mo/yr
|
$5.18 |
Electricity Fees | $10,737 | - |
|
- |
Natural Gas | $231,508 | 44,067 |
MMBtu
|
$5.25 |
TOTAL YEARLY COSTS | $1,106,691 | |||
RECOMMENDED SAVINGS* | $108,000 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $94,556 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.6231: Utilize controls to operate equipment only when needed | $10,718 | - |
$10,718
102,080
kWh
|
- | |
02 | 2.7314: Reduce ventilation air | $1,234 | - |
$594
5,653
kWh
|
$640
-
MMBtu
|
|
03 | 2.6122: Adjust vents to minimize energy use | $2,053 | - |
$578
5,500
kWh
|
$1,475
-
MMBtu
|
|
04 | 2.7314: Reduce ventilation air | $2,739 | - |
$770
7,333
kWh
|
$1,969
-
MMBtu
|
|
05 | 2.2443: Re-use or recycle hot or cold process exhaust air | $4,421 | $3,000 | - |
$4,421
-
MMBtu
|
|
06 | 2.6231: Utilize controls to operate equipment only when needed | $12,451 | - |
$12,451
118,581
kWh
|
- | |
07 | 2.7314: Reduce ventilation air | $1,643 | $57 |
$462
4,400
kWh
|
$1,181
-
MMBtu
|
|
08 | 2.2443: Re-use or recycle hot or cold process exhaust air | $6,284 | $3,000 | - |
$6,284
-
MMBtu
|
|
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,355 | $9,585 |
$10,355
98,622
kWh
|
- | |
10 | 2.5111: Convert from indirect to direct fired systems | $56,102 | $91,218 | - |
$56,102
-
MMBtu
|
|
TOTAL RECOMMENDED | $108,000 | $106,860 |
$35,928
342,169
kWh
|
$72,072
-
MMBtu
|
||
TOTAL IMPLEMENTED | $94,556 | $100,860 |
$35,158
334,836
kWh
|
$59,398
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs