Assessment Year | 2016 |
---|---|
Principal Product | Composite Armour |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 3624: Carbon and Graphite Products |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
250,000
ft2
|
Annual Production | 40,000
units
|
Production Hrs. Annual | 3,432
hrs
|
Location (State) | Maryland |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $135,427 | 2,316,475 |
kWh
|
$0.058 | |
Electricity Demand | $51,934 | 9,170 |
kW-mo/yr
|
$5.66 | |
Electricity Fees | $11,460 | - |
|
- | |
Fuel Oil #1 | $42,351 | 2,672 |
MMBtu
|
$15.85 | |
Waste Disposal Costs | |||||
Water Usage | $12,477 | 903,210 |
Tgal
|
$0.014 | |
TOTAL YEARLY COSTS | $253,649 | ||||
RECOMMENDED SAVINGS* | $39,309 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $7,289 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Fuel Oil #1 Savings |
---|---|---|---|---|---|---|
01 | 4.444: Install system to collect scrap | $4,328 | $360 |
$4,328
53,428
kWh
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,059 | $4,224 |
$4,059
50,115
kWh
|
- | |
03 | 2.7263: Lower compressor pressure through a/c system modification | $374 | - |
$374
4,613
kWh
|
- | |
04 | 2.4322: Use or replace with energy efficient substitutes | $2,863 | $11,400 |
$2,863
35,346
kWh
|
- | |
05 | 2.4322: Use or replace with energy efficient substitutes | $2,572 | $11,400 |
$2,572
31,747
kWh
|
- | |
06 | 2.2437: Recover waste heat from equipment | $2,076 | $431 | - |
$2,076
-
MMBtu
|
|
07 | 2.7224: Reduce space conditioning during non-working hours | $2,885 | - | - |
$2,885
-
MMBtu
|
|
08 | 2.2437: Recover waste heat from equipment | $6,911 | $588 |
$571
7,050
kWh
|
$6,340
-
MMBtu
|
|
09 | 2.1123: Install automatic stack damper | $624 | $205 | - |
$624
-
MMBtu
|
|
10 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $2,505 | $1,524 |
$2,505
30,900
kWh
|
- | |
11 | 2.6231: Utilize controls to operate equipment only when needed | $5,192 | $3,840 |
$5,192
64,100
kWh
|
- | |
12 | 2.6218: Turn off equipment when not in use | $4,030 | - |
$4,030
49,764
kWh
|
- | |
13 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $890 | $4,170 |
$890
15,340
kWh
|
- | |
TOTAL RECOMMENDED | $39,309 | $38,142 |
$27,384
342,403
kWh
|
$11,925
-
MMBtu
|
||
TOTAL IMPLEMENTED | $7,289 | - |
$4,404
54,377
kWh
|
$2,885
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Fuel Oil #1 Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs