| Assessment Year | 2013 |
|---|---|
| Principal Product | Wire cloth, metal belting |
| NAICS | 332618: Other Fabricated Wire Product Manufacturing |
| SIC | 3496: Miscellaneous Fabricated Wire Products |
| Sales Range | $50 M to 100M |
| # of Employees | 50 |
| Plant Area |
346,000
ft2
|
| Annual Production | 9,999
units
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Maryland |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $346,133 | 5,069,553 |
kWh
|
$0.068 |
| Electricity Demand | $68,457 | 12,758 |
kW-mo/yr
|
$5.37 |
| LPG | $45,433 | 2,564 |
MMBtu
|
$17.72 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $118,501 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | LPG Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,410 | $2,000 |
$7,410
88,223
kWh
|
- | - | |
| 02 | 2.2437: Recover waste heat from equipment | $12,684 | $2,350 | - | - |
$12,684
-
MMBtu
|
|
| 03 | 2.2437: Recover waste heat from equipment | $11,278 | $2,350 |
$11,278
134,260
kWh
|
- | - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,080 | $500 |
$2,080
24,774
kWh
|
- | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,930 | $2,000 |
$5,930
70,577
kWh
|
- | - | |
| 06 | 2.1332: Convert combustion equipment to burn natural gas | $27,486 | $11,000 | - |
$(-17,948.0)
-
MMBtu
|
$45,434
-
MMBtu
|
|
| 07 | 2.7444: Close holes and openings in building such as broken windows | $10,394 | $7,600 |
$10,394
123,739
kWh
|
- | - | |
| 08 | 2.7134: Use photocell controls | $100 | $85 |
$100
1,190
kWh
|
- | - | |
| 09 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $41,139 | $70,800 |
$63,840
760,000
kWh
|
$(-22,701.0)
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $118,501 | $98,685 |
$101,032
1,202,763
kWh
|
$(-40,649.0)
-
MMBtu
|
$58,118
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | LPG Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs