| Assessment Year | 2011 |
|---|---|
| Principal Product | Baby Wipes |
| NAICS | 322291: Sanitary Paper Product Manufacturing |
| SIC | 2676: Sanitary Paper Products |
| Sales Range | $100 M to 500M |
| # of Employees | 470 |
| Plant Area |
450,000
ft2
|
| Annual Production | 16,200,000
pieces
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Delaware |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,712,944 | 15,750,000 |
kWh
|
$0.11 |
| Natural Gas | $14,714 | 1,051 |
MMBtu
|
$14.00 |
| Other Energy | $221,196 | 16,746 |
MMBtu
|
$13.21 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $335,843 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $288,870 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Other Energy Savings | Water Consumption Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4226: Use / purchase optimum sized compressor | $136,635 | $120,000 |
$136,635
1,235,538
kWh
|
- | - | |
| 02 | 2.7314: Reduce ventilation air | $12,200 | $200 |
$1,800
16,700
kWh
|
$10,400
-
MMBtu
|
- | |
| 03 | 2.7314: Reduce ventilation air | $2,160 | $45 |
$320
2,960
kWh
|
$1,840
-
MMBtu
|
- | |
| 04 | 2.6242: Minimize operation of equipment maintained in standby condition | $14,330 | $500 |
$14,330
131,490
kWh
|
- | - | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,782 | $1,800 |
$1,782
16,350
kWh
|
- | - | |
| 06 | 2.2622: Replace existing chiller with high efficiency model | $104,177 | $157,000 |
$104,177
955,750
kWh
|
- | - | |
| 07 | 2.1393: Use steam sparging or injections in place of indirect heating | $4,600 | $10,000 | - |
$3,800
-
MMBtu
|
$800
-
Tgal
|
|
| 08 | 2.2611: Moderate cooling tower outlet temperature | $21,528 | $52,000 |
$21,528
197,500
kWh
|
- | - | |
| 09 | 2.7243: Improve air circulation with destratification fans / other methods | $4,701 | $10,500 |
$(-1,177.2)
(-10,800)
kWh
|
$5,879
-
MMBtu
|
- | |
| 10 | 2.9114: Use solar heat to make electricty | $33,730 | $1,035,000 |
$33,730
309,450
kWh
|
- | - | |
| TOTAL RECOMMENDED | $335,843 | $1,387,045 |
$313,125
2,854,938
kWh
|
$21,919
-
MMBtu
|
$800
-
Tgal
|
||
| TOTAL IMPLEMENTED | $288,870 | $329,700 |
$278,470
2,536,978
kWh
|
$10,400
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Other Energy Savings | Water Consumption Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs