Assessment Year 2010
Principal Product Polishing products
NAICS 313310: Textile and Fabric Finishing Mills
SIC 2269: Finishers of Textiles, Not elsewhere Classified
Sales Range $100
M
to 500
M
# of Employees 650
Plant Area 6,500
ft2
Annual Production 1
units
Production Hrs. Annual 6,120
hrs
Location (State) Delaware

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $770,578 6,124,800
kWh
Natural Gas $547,652 75,921
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $276,712 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $51,250

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.7228: Avoid introducing hot, humid, or dirty air into hvac system $143,000 $81,500 $143,000
1,136,000
kWh
-
02 2.7313: Recycle air for heating, ventilation and air conditioning $53,946 $10,848 - $53,946
-
MMBtu
03 2.7142: Utilize higher efficiency lamps and/or ballasts $25,100 $24,000 $25,100
200,000
kWh
-
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $15,250 $9,000 $15,250
121,065
kWh
-
05 2.6231: Utilize controls to operate equipment only when needed $12,940 $1,500 $12,940
102,724
kWh
-
06 2.7142: Utilize higher efficiency lamps and/or ballasts $11,040 $720 $11,040
87,600
kWh
-
07 2.7111: Reduce illumination to minimum necessary levels $4,560 $200 $4,560
36,200
kWh
-
08 2.7135: Install occupancy sensors $3,810 $560 $3,810
30,240
kWh
-
09 2.4111: Utilize energy-efficient belts and other improved mechanisms $3,650 $1,019 $3,650
29,000
kWh
-
10 2.6231: Utilize controls to operate equipment only when needed $3,106 $495 $3,106
24,650
kWh
-
11 2.7314: Reduce ventilation air $310 $585 $310
2,474
kWh
-
TOTAL RECOMMENDED $276,712 $130,427 $222,766
1,769,953
kWh
$53,946
-
MMBtu
TOTAL IMPLEMENTED $51,250 $12,999 $51,250
406,829
kWh
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs