| Assessment Year | 2010 |
|---|---|
| Principal Product | Laser optics and assemblies |
| NAICS | 333314: Optical Instrument and Lens Manufacturing |
| SIC | 3827: Optical Instruments and Lenses |
| Sales Range | $10 M to 50M |
| # of Employees | 180 |
| Plant Area |
65,000
ft2
|
| Annual Production | 780
pieces
|
| Production Hrs. Annual | 4,680
hrs
|
| Location (State) | New Mexico |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $121,057 | 2,687,904 |
kWh
|
$0.045 |
| Electricity Demand | $92,046 | 6,286 |
kW-mo/yr
|
$14.64 |
| Natural Gas | $4,786 | 589 |
MMBtu
|
$8.13 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $24,040 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,720 | $410 |
$2,300
44,100
kWh
|
$1,420
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,220 | $3,400 |
$880
18,900
kWh
|
$340
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,910 | $5,160 |
$3,290
58,300
kWh
|
$2,690
-
kW-mo/yr
|
$70 | - | $(-140.0) | |
| 04 | 2.9114: Use solar heat to make electricty | $4,170 | $31,500 |
$1,020
16,800
kWh
|
$850
-
kW-mo/yr
|
- | $2,300 | - | |
| 05 | 2.6231: Utilize controls to operate equipment only when needed | $3,610 | $2,880 |
$3,610
78,300
kWh
|
- | - | - | - | |
| 06 | 2.7232: Replace existing hvac unit with high efficiency model | $3,270 | $35,500 |
$2,650
53,300
kWh
|
$620
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,300 | $5,160 |
$670
12,800
kWh
|
$410
-
kW-mo/yr
|
$130 | - | $90 | |
| 08 | 2.7135: Install occupancy sensors | $520 | $810 |
$280
4,800
kWh
|
$230
-
kW-mo/yr
|
- | - | $10 | |
| 09 | 2.6211: Conserve energy by efficient use of vending machines | $320 | $650 |
$280
6,100
kWh
|
$40
-
kW-mo/yr
|
- | - | - | |
| TOTAL RECOMMENDED | $24,040 | $85,470 |
$14,980
293,400
kWh
|
$6,600
-
kW-mo/yr
|
$200 | $2,300 | $(-40.0) | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs