Assessment Year | 2014 |
---|---|
Principal Product | Aluminum Diecasting |
NAICS | 331523: Nonferrous Metal Die-Casting Foundries |
SIC | 3363: Aluminum Die-Castings |
Sales Range | $10 M to 50M |
# of Employees | 145 |
Plant Area |
65,000
ft2
|
Annual Production | 3,500
ton
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $570,935 | 8,191,800 |
kWh
|
$0.070 |
Electricity Demand | $228,884 | 17,100 |
kW-mo/yr
|
$13.39 |
Electricity Fees | $(-25,701.0) | - |
|
- |
Natural Gas | $348,239 | 51,821 |
MMBtu
|
$6.72 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $195,305 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,855 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2414: Use waste heat from hot flue gases to preheat | $71,098 | $51,000 | - | - |
$71,098
-
MMBtu
|
- | - | |
02 | 2.2211: Use optimum temperature | $55,730 | - | - | - |
$55,730
-
MMBtu
|
- | - | |
03 | 2.8114: Change rate schedules or other changes in utility service | $44,848 | $200,000 | - | - | - | - | $44,848 | |
04 | 2.4322: Use or replace with energy efficient substitutes | $7,464 | $602 |
$7,464
107,092
kWh
|
- | - | - | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $6,689 | $608 |
$5,115
73,382
kWh
|
$1,574
-
kW-mo/yr
|
- | - | - | |
06 | 2.4322: Use or replace with energy efficient substitutes | $6,489 | $9,750 |
$6,489
70,862
kWh
|
- | - | - | - | |
07 | 2.2511: Insulate bare equipment | $2,595 | $2,500 |
$2,285
32,815
kWh
|
- | - |
$310
-
Tgal
|
- | |
08 | 2.7135: Install occupancy sensors | $391 | $375 |
$391
5,616
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $195,305 | $264,835 |
$21,744
289,767
kWh
|
$1,574
-
kW-mo/yr
|
$126,828
-
MMBtu
|
$310
-
Tgal
|
$44,848 | ||
TOTAL IMPLEMENTED | $7,855 | $977 |
$7,855
112,708
kWh
|
- | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs