| Assessment Year | 2009 |
|---|---|
| Principal Product | Doors |
| NAICS | 321911: Wood Window and Door Manufacturing |
| SIC | 2431: Millwork |
| Sales Range | $10 M to 50M |
| # of Employees | 160 |
| Plant Area |
36,000
ft2
|
| Annual Production | 173,000
pieces
|
| Production Hrs. Annual | 6,552
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $127,594 | 3,092,160 |
kWh
|
$0.041 |
| Electricity Demand | $79,112 | 5,191 |
kW-mo/yr
|
$15.24 |
| Electricity Fees | $341 | - |
|
- |
| Natural Gas | $22,611 | 2,666 |
MMBtu
|
$8.48 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $25,150 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,470 | $10,470 |
$5,670
153,600
kWh
|
$4,800
-
kW-mo/yr
|
|
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,540 | $1,000 |
$4,160
112,600
kWh
|
$3,380
-
kW-mo/yr
|
|
| 03 | 2.4239: Eliminate or reduce compressed air usage | $5,500 | $110 |
$3,660
99,300
kWh
|
$1,840
-
kW-mo/yr
|
|
| 04 | 2.4224: Upgrade controls on compressors | $1,640 | $70 |
$650
17,600
kWh
|
$990
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $25,150 | $11,650 |
$14,140
383,100
kWh
|
$11,010
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs