| Assessment Year | 2007 |
|---|---|
| Principal Product | Prime mover controls |
| NAICS | 311999: All Other Miscellaneous Food Manufacturing |
| SIC | 3625: Relays and Industrial Controls |
| Sales Range | $50 M to 100M |
| # of Employees | 1,000 |
| Plant Area |
223,000
ft2
|
| Annual Production | 1,000,000
pieces
|
| Production Hrs. Annual | 3,744
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $283,225 | 15,625,400 |
kWh
|
$0.018 |
| Electricity Demand | $417,648 | 53,228 |
kW-mo/yr
|
$7.85 |
| Electricity Fees | $384 | - |
|
- |
| Natural Gas | $200,926 | 23,908 |
MMBtu
|
$8.40 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $43,650 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $43,650 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4224: Upgrade controls on compressors | $11,650 | $56,600 |
$5,190
278,300
kWh
|
$6,460
-
kW-mo/yr
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,530 | $1,500 |
$2,060
110,500
kWh
|
$2,470
-
kW-mo/yr
|
- | |
| 03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,470 | $60 |
$1,780
95,300
kWh
|
$1,690
-
kW-mo/yr
|
- | |
| 04 | 2.1224: Replace boiler | $23,660 | $20,000 |
$1,890
101,300
kWh
|
$2,230
-
kW-mo/yr
|
$19,540
-
MMBtu
|
|
| 05 | 2.7135: Install occupancy sensors | $340 | $1,370 |
$280
14,800
kWh
|
$60
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $43,650 | $79,530 |
$11,200
600,200
kWh
|
$12,910
-
kW-mo/yr
|
$19,540
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $43,650 | $79,530 |
$11,200
600,200
kWh
|
$12,910
-
kW-mo/yr
|
$19,540
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs