| Assessment Year | 2006 |
|---|---|
| Principal Product | Electronic circuit boards, assemblies |
| NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
| SIC | 3679: Electronic Components, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 135 |
| Plant Area |
109,835
ft2
|
| Annual Production | 1,000,000
pieces
|
| Production Hrs. Annual | 5,590
hrs
|
| Location (State) | New Mexico |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $118,073 | 2,942,400 |
kWh
|
$0.040 |
| Electricity Demand | $21,709 | 7,956 |
kW-mo/yr
|
$2.73 |
| Electricity Fees | $66,622 | - |
|
- |
| Natural Gas | $22,243 | 1,927 |
MMBtu
|
$11.54 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $14,540 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $3,350 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,430 | $200 |
$1,540
38,000
kWh
|
$890
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.6218: Turn off equipment when not in use | $610 | - |
$610
19,300
kWh
|
- | - | - | - | |
| 03 | 2.4226: Use / purchase optimum sized compressor | $260 | $30 |
$160
4,000
kWh
|
$100
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,680 | $5,290 |
$3,310
76,100
kWh
|
$2,120
-
kW-mo/yr
|
$70 | - | $180 | |
| 05 | 2.9114: Use solar heat to make electricty | $3,900 | $32,600 |
$1,090
23,000
kWh
|
$870
-
kW-mo/yr
|
- | $1,940 | - | |
| 06 | 2.7135: Install occupancy sensors | $1,350 | $1,290 |
$800
18,500
kWh
|
$480
-
kW-mo/yr
|
$30 | - | $40 | |
| 07 | 2.7122: Disconnect ballasts | $310 | $110 |
$170
3,900
kWh
|
$120
-
kW-mo/yr
|
$10 | - | $10 | |
| TOTAL RECOMMENDED | $14,540 | $39,520 |
$7,680
182,800
kWh
|
$4,580
-
kW-mo/yr
|
$110 | $1,940 | $230 | ||
| TOTAL IMPLEMENTED | $3,350 | $310 |
$2,320
61,200
kWh
|
$1,010
-
kW-mo/yr
|
$10 | - | $10 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs