Assessment Year | 2003 |
---|---|
Principal Product | Thin-film coating machines |
NAICS | 333249: Other Industrial Machinery Manufacturing |
SIC | 3559: Special Industry Machinery, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
60,000
ft2
|
Annual Production | 6
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $87,379 | 4,001,333 |
kWh
|
$0.022 |
Electricity Demand | $114,937 | 9,196 |
kW-mo/yr
|
$12.50 |
Electricity Fees | $180 | - |
|
- |
Natural Gas | $3,605 | 900 |
MMBtu
|
$4.01 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $24,721 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,800 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,330 | $19,000 | n/a |
$5,670
188,400
kWh
|
$4,540
-
kW-mo/yr
|
$80 | $(-960.0) |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,800 | $930 |
$4,330
143,800
kWh
|
$2,470
-
kW-mo/yr
|
- | - | |
03 | 2.4226: Use / purchase optimum sized compressor | $2,520 | $2,300 |
$2,520
83,600
kWh
|
- | - | - | |
04 | 2.7135: Install occupancy sensors | $1,690 | $6,230 |
$840
27,800
kWh
|
$680
-
kW-mo/yr
|
$80 | $90 | |
05 | 2.7135: Install occupancy sensors | $1,520 | $1,070 |
$760
24,900
kWh
|
$650
-
kW-mo/yr
|
$30 | $80 | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,171 | $656 |
$823
27,331
kWh
|
$657
-
kW-mo/yr
|
- | $(-309.0) | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $980 | $2,750 |
$610
20,100
kWh
|
$370
-
kW-mo/yr
|
- | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $710 | $620 |
$450
15,000
kWh
|
$260
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $24,721 | $33,556 |
$16,003
530,931
kWh
|
$9,627
-
kW-mo/yr
|
$190 | $(-1,099.0) | ||
TOTAL IMPLEMENTED | $6,800 | $930 |
$4,330
143,800
kWh
|
$2,470
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs