Assessment Year | 2002 |
---|---|
Principal Product | Assembled electronic components |
NAICS |
n/a
|
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 1,080 |
Plant Area |
360,000
ft2
|
Annual Production | 865,600
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $562,372 | 15,681,280 |
kWh
|
$0.036 |
Electricity Demand | $156,005 | 26,000 |
kW-mo/yr
|
$6.00 |
Electricity Fees | $2,454 | - |
|
- |
Natural Gas | $162,056 | 19,513 |
MMBtu
|
$8.31 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $106,041 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $85,338 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7252: Utilize an evaporative air pre-cooler or other heat exchanger in ac system | $51,590 | $6,250 |
$38,600
1,033,100
kWh
|
$12,990
-
kW-mo/yr
|
- | - | - | |
02 | 2.7224: Reduce space conditioning during non-working hours | $25,940 | - |
$25,940
663,700
kWh
|
- | - | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,053 | - |
$30,900
822,000
kWh
|
$10,370
-
kW-mo/yr
|
$(-1,902.0) | $(-27,315.0) | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,310 | $430 |
$5,830
157,500
kWh
|
$1,660
-
kW-mo/yr
|
$(-180.0) | - | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $3,730 | $870 |
$2,900
78,300
kWh
|
$830
-
kW-mo/yr
|
- | - | - | |
06 | 2.7135: Install occupancy sensors | $2,760 | $3,360 |
$2,760
74,500
kWh
|
- | - | - | - | |
07 | 2.4133: Use most efficient type of electric motors | $498 | $946 |
$380
10,240
kWh
|
$118
-
kW-mo/yr
|
- | - | - | |
08 | 2.7134: Use photocell controls | $2,160 | $2,040 |
$1,150
31,100
kWh
|
$910
-
kW-mo/yr
|
- | - | $100 | |
TOTAL RECOMMENDED | $106,041 | $13,896 |
$108,460
2,870,440
kWh
|
$26,878
-
kW-mo/yr
|
$(-2,082.0) | $(-27,315.0) | $100 | ||
TOTAL IMPLEMENTED | $85,338 | $7,626 |
$70,750
1,864,540
kWh
|
$14,768
-
kW-mo/yr
|
$(-180.0) | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs