Assessment Year | 2000 |
---|---|
Principal Product | finished household furniture |
NAICS |
n/a
|
SIC | 2511: Wood Household Furniture, Except Upholstered |
Sales Range | $5 M to 10M |
# of Employees | 75 |
Plant Area |
31,000
ft2
|
Annual Production | 10,000
pieces
|
Production Hrs. Annual | 4,290
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $14,850 | 995,604 |
kWh
|
$0.015 |
Electricity Demand | $34,811 | 3,274 |
kW-mo/yr
|
$10.63 |
Natural Gas | $14,689 | 3,324 |
MMBtu
|
$4.42 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $44,390 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $41,300 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $4,280 | $12,550 | - | - |
$4,280
-
MMBtu
|
- | - | - | - | |
02 | 2.3191: Use demand controller or load shedder | $2,960 | $200 | - |
$3,440
-
kW-mo/yr
|
- | - | $(-480.0) | - | - | |
03 | 2.7442: Keep doors and windows shut when not on use | $1,040 | $1,000 | - | - |
$1,040
-
MMBtu
|
- | - | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $570 | $370 |
$310
20,809
kWh
|
$620
-
kW-mo/yr
|
- | $(-360.0) | - | - | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $410 | $1,020 |
$140
9,379
kWh
|
$270
-
kW-mo/yr
|
- | - | - | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $130 | - |
$80
5,569
kWh
|
$210
-
kW-mo/yr
|
- | - | - | $(-160.0) | - | |
07 | 4.431: Train operators for maximum operating efficiency | $35,000 | $1,600 | - | - | - | - | - | - | $35,000 | |
TOTAL RECOMMENDED | $44,390 | $16,740 |
$530
35,757
kWh
|
$4,540
-
kW-mo/yr
|
$5,320
-
MMBtu
|
$(-360.0) | $(-480.0) | $(-160.0) | $35,000 | ||
TOTAL IMPLEMENTED | $41,300 | $16,540 |
$450
30,188
kWh
|
$890
-
kW-mo/yr
|
$5,320
-
MMBtu
|
$(-360.0) | - | - | $35,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs