Assessment Year | 1997 |
---|---|
Principal Product | dried bean products |
NAICS |
n/a
|
SIC | 2034: Dried and Dehydrated Fruits, Vegetables, and Soup Mixes |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
52,130
ft2
|
Annual Production | 19,000,000
thousand feet
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $27,672 | 1,483,880 |
kWh
|
$0.019 |
Electricity Demand | $43,324 | 2,846 |
kW-mo/yr
|
$15.22 |
Electricity Fees | $156 | - |
|
- |
Natural Gas | $184,777 | 68,366 |
MMBtu
|
$2.70 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $77,179 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $77,179 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Primary Product Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.2437: Recover waste heat from equipment | $6,360 | $8,400 |
$(-180.0)
(-9,965)
kWh
|
$(-280.0)
-
kW-mo/yr
|
$6,820
-
MMBtu
|
- | - | - | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,130 | $1,500 | - | - |
$2,130
-
MMBtu
|
- | - | - | |
03 | 2.4133: Use most efficient type of electric motors | $289 | $288 |
$115
6,155
kWh
|
$174
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.2135: Repair and eliminate steam leaks | $670 | $140 | - | - |
$670
-
MMBtu
|
- | - | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $380 | $430 |
$150
8,499
kWh
|
$230
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $220 | $290 |
$90
4,689
kWh
|
$130
-
kW-mo/yr
|
- | - | - | - | |
07 | 3.3122: Use filtration, centrifuging to remove contaminants | $18,030 | $4,000 | - | - | - |
$18,030
-
Tgal
|
- | - | |
08 | 4.651: Install back-up equipment | $33,500 | $90,000 | - | - | - | - | - | $33,500 | |
09 | 4.123: Reduce defects by reducing product tipping | $15,600 | $21,000 | - | - | - | - | $15,600 | - | |
TOTAL RECOMMENDED | $77,179 | $126,048 |
$175
9,378
kWh
|
$254
-
kW-mo/yr
|
$9,620
-
MMBtu
|
$18,030
-
Tgal
|
$15,600 | $33,500 | ||
TOTAL IMPLEMENTED | $77,179 | $126,048 |
$175
9,378
kWh
|
$254
-
kW-mo/yr
|
$9,620
-
MMBtu
|
$18,030
-
Tgal
|
$15,600 | $33,500 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Primary Product Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs