Assessment Year | 1996 |
---|---|
Principal Product | unfinished center pivot irrigation systems |
NAICS |
n/a
|
SIC | 3523: Farm Machinery and Equipment |
Sales Range | $50 M to 100M |
# of Employees | 250 |
Plant Area |
164,500
ft2
|
Annual Production | 10,000
ton
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Nebraska |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $163,977 | 7,674,092 |
kWh
|
$0.021 |
Electricity Demand | $133,316 | 17,816 |
kW-mo/yr
|
$7.48 |
Electricity Fees | $363 | - |
|
- |
Natural Gas | $131,129 | 49,826 |
MMBtu
|
$2.63 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,368 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $23,305 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7231: Use radiant heater for spot heating | $13,520 | $6,200 |
$18,200
469,226
kWh
|
- |
$(-4,680.0)
-
MMBtu
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,200 | $160 |
$2,690
125,733
kWh
|
$1,510
-
kW-mo/yr
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,063 | $4,806 |
$1,150
53,634
kWh
|
$913
-
kW-mo/yr
|
- | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $2,640 | $1,870 |
$1,690
79,132
kWh
|
$950
-
kW-mo/yr
|
- | - | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,110 | $40 |
$710
33,118
kWh
|
$400
-
kW-mo/yr
|
- | - | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,030 | $1,080 |
$700
32,825
kWh
|
$330
-
kW-mo/yr
|
- | - | - | |
07 | 2.4133: Use most efficient type of electric motors | $155 | $187 |
$105
4,982
kWh
|
$50
-
kW-mo/yr
|
- | - | - | |
08 | 3.8132: Use less toxic and volatile solvent substitutes | $650 | $1,580 | - | - | - |
$1,010
-
gal
|
$(-360.0) | |
TOTAL RECOMMENDED | $25,368 | $15,923 |
$25,245
798,650
kWh
|
$4,153
-
kW-mo/yr
|
$(-4,680.0)
-
MMBtu
|
$1,010
-
gal
|
$(-360.0) | ||
TOTAL IMPLEMENTED | $23,305 | $11,117 |
$24,095
745,016
kWh
|
$3,240
-
kW-mo/yr
|
$(-4,680.0)
-
MMBtu
|
$1,010
-
gal
|
$(-360.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs