Assessment Year 1996
Principal Product unfinished center pivot irrigation systems
NAICS
n/a
SIC 3523: Farm Machinery and Equipment
Sales Range $50
M
to 100
M
# of Employees 250
Plant Area 164,500
ft2
Annual Production 10,000
ton
Production Hrs. Annual 7,488
hrs
Location (State) Nebraska

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $163,977 7,674,092
kWh
Electricity Demand $133,316 17,816
kW-mo/yr
Electricity Fees $363 -
Natural Gas $131,129 49,826
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $25,368 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $23,305

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (haz) Savings Ancillary Material Cost Savings
01 2.7231: Use radiant heater for spot heating $13,520 $6,200 $18,200
469,226
kWh
- $(-4,680.0)
-
MMBtu
- -
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $4,200 $160 $2,690
125,733
kWh
$1,510
-
kW-mo/yr
- - -
03 2.7142: Utilize higher efficiency lamps and/or ballasts $2,063 $4,806 $1,150
53,634
kWh
$913
-
kW-mo/yr
- - -
04 2.4221: Install compressor air intakes in coolest locations $2,640 $1,870 $1,690
79,132
kWh
$950
-
kW-mo/yr
- - -
05 2.4221: Install compressor air intakes in coolest locations $1,110 $40 $710
33,118
kWh
$400
-
kW-mo/yr
- - -
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,030 $1,080 $700
32,825
kWh
$330
-
kW-mo/yr
- - -
07 2.4133: Use most efficient type of electric motors $155 $187 $105
4,982
kWh
$50
-
kW-mo/yr
- - -
08 3.8132: Use less toxic and volatile solvent substitutes $650 $1,580 - - - $1,010
-
gal
$(-360.0)
TOTAL RECOMMENDED $25,368 $15,923 $25,245
798,650
kWh
$4,153
-
kW-mo/yr
$(-4,680.0)
-
MMBtu
$1,010
-
gal
$(-360.0)
TOTAL IMPLEMENTED $23,305 $11,117 $24,095
745,016
kWh
$3,240
-
kW-mo/yr
$(-4,680.0)
-
MMBtu
$1,010
-
gal
$(-360.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (haz) Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs