| Assessment Year | 1994 |
|---|---|
| Principal Product | Aerospace Parts |
| NAICS |
n/a
|
| SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 176 |
| Plant Area |
140,000
ft2
|
| Annual Production | 110,300
pieces
|
| Production Hrs. Annual | 7,320
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $285,070 | 5,990,328 |
kWh
|
$0.048 |
| Natural Gas | $12,460 | 3,002 |
MMBtu
|
$4.15 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $50,680 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $9,100 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 3.5146: Utilize a central coolant system for cleaning and reuse of metal working fluid | $21,300 | $16,000 |
$4,420
108,734
kWh
|
- |
$16,880
-
gal
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,150 | $34,110 |
$11,150
234,174
kWh
|
- | - | - | |
| 03 | 2.4133: Use most efficient type of electric motors | $5,820 | $3,430 |
$5,820
122,216
kWh
|
- | - | - | |
| 04 | 3.7132: Reuse rags until completely soiled | $4,520 | $1,160 | - | - | - |
$4,520
-
lb
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,280 | $3,260 |
$3,280
68,875
kWh
|
- | - | - | |
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,200 | $5,880 |
$3,200
67,409
kWh
|
- | - | - | |
| 07 | 2.6231: Utilize controls to operate equipment only when needed | $1,120 | $920 |
$980
20,809
kWh
|
$140
-
MMBtu
|
- | - | |
| 08 | 2.7224: Reduce space conditioning during non-working hours | $290 | $530 |
$200
7,913
kWh
|
$90
-
MMBtu
|
- | - | |
| TOTAL RECOMMENDED | $50,680 | $65,290 |
$29,050
630,130
kWh
|
$230
-
MMBtu
|
$16,880
-
gal
|
$4,520
-
lb
|
||
| TOTAL IMPLEMENTED | $9,100 | $6,690 |
$9,100
191,091
kWh
|
- | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs