| Assessment Year | 1990 |
|---|---|
| Principal Product | POTATO AND CORN CHIPS |
| NAICS |
n/a
|
| SIC | 2096: Potato Chips, Corn Chips, and Similar Snacks |
| Sales Range | $10 M to 50M |
| # of Employees | 140 |
| Plant Area |
n/a
|
| Annual Production | 20,000,000
lb
|
| Production Hrs. Annual | 7,280
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $179,551 | 3,681,712 |
kWh
|
$0.049 |
| Natural Gas | $304,572 | 114,977 |
MMBtu
|
$2.65 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $20,746 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,500 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2414: Use waste heat from hot flue gases to preheat | $8,700 | $18,000 | - |
$8,700
-
MMBtu
|
|
| 02 | 2.4133: Use most efficient type of electric motors | $946 | $1,055 |
$946
19,343
kWh
|
- | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $3,500 | $1,000 |
$3,500
72,392
kWh
|
- | |
| 04 | 2.2437: Recover waste heat from equipment | $2,700 | $7,000 | - |
$2,700
-
MMBtu
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,900 | $500 |
$1,900
38,101
kWh
|
- | |
| 06 | 2.4239: Eliminate or reduce compressed air usage | $3,000 | $6,000 |
$3,000
120,750
kWh
|
- | |
| TOTAL RECOMMENDED | $20,746 | $33,555 |
$9,346
250,586
kWh
|
$11,400
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $6,500 | $7,000 |
$6,500
193,142
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs