| Assessment Year | 1990 |
|---|---|
| Principal Product | CIRCUIT COMPUTER CHIPS |
| NAICS |
n/a
|
| SIC | 3674: Semiconductors and Related Devices |
| Sales Range | $10 M to 50M |
| # of Employees | 300 |
| Plant Area |
n/a
|
| Annual Production | 70
pieces
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $638,224 | 16,844,080 |
kWh
|
$0.038 |
| Natural Gas | $176,704 | 48,222 |
MMBtu
|
$3.66 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $50,110 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $24,970 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2623: Minimize condenser cooling water temperature | $7,600 | $500 |
$7,600
201,348
kWh
|
- | |
| 02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $6,500 | $4,000 | - |
$6,500
-
MMBtu
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,630 | $12,700 |
$3,630
95,838
kWh
|
- | |
| 04 | 2.7229: Air condition only space necessary | $8,590 | $1,300 |
$7,040
264,068
kWh
|
$1,550
-
MMBtu
|
|
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,320 | $3,670 |
$3,320
87,046
kWh
|
- | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $2,280 | $2,100 |
$2,280
60,375
kWh
|
- | |
| 07 | 2.3212: Optimize plant power factor | $18,190 | $20,700 |
$18,190
-
kWh
|
- | |
| TOTAL RECOMMENDED | $50,110 | $44,970 |
$42,060
708,675
kWh
|
$8,050
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $24,970 | $7,900 |
$16,920
525,791
kWh
|
$8,050
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs