| Assessment Year | 1990 |
|---|---|
| Principal Product | FLUID MILK & SOFT DRINKS |
| NAICS |
n/a
|
| SIC | 2026: Fluid Milk |
| Sales Range | $10 M to 50M |
| # of Employees | 35 |
| Plant Area |
n/a
|
| Annual Production | 9,400
Tgal
|
| Production Hrs. Annual | 4,004
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $133,947 | 2,064,478 |
kWh
|
$0.065 |
| Natural Gas | $68,392 | 12,277 |
MMBtu
|
$5.57 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $8,758 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,758 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $4,400 | $1,500 | - |
$4,400
-
MMBtu
|
- | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $1,400 | $500 |
$1,400
21,688
kWh
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $358 | $339 |
$358
5,569
kWh
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $120 | $700 |
$120
1,758
kWh
|
- | - | |
| 05 | 3.4154: Eliminate leaks in water lines and valves | $2,480 | $350 | - |
$1,987
-
MMBtu
|
$493 | |
| TOTAL RECOMMENDED | $8,758 | $3,389 |
$1,878
29,015
kWh
|
$6,387
-
MMBtu
|
$493 | ||
| TOTAL IMPLEMENTED | $8,758 | $3,389 |
$1,878
29,015
kWh
|
$6,387
-
MMBtu
|
$493 | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs