Assessment Year | 1989 |
---|---|
Principal Product | HARD CANDY |
NAICS |
n/a
|
SIC | 2064: Candy and Other Confectionery Products |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
n/a
|
Annual Production | 32,000,000
lb
|
Production Hrs. Annual | 4,680
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $171,571 | 3,210,141 |
kWh
|
$0.053 |
Natural Gas | $112,266 | 40,013 |
MMBtu
|
$2.81 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,978 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,638 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.2711: Utilize outside air instead of conditioned air for drying | $1,370 | $3,200 |
$1,370
55,100
kWh
|
- | |
02 | 2.3132: Recharge batteries on during off-peak demand periods | $660 | $500 |
$660
-
kWh
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $2,760 | $1,000 |
$2,760
51,583
kWh
|
- | |
04 | 2.7243: Improve air circulation with destratification fans / other methods | $1,273 | $3,850 |
$(-97.0)
(-1,758)
kWh
|
$1,370
-
MMBtu
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $900 | $776 |
$900
16,706
kWh
|
- | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $2,670 | $6,111 |
$2,670
49,824
kWh
|
- | |
07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,460 | $1,000 | - |
$1,460
-
MMBtu
|
|
08 | 2.4133: Use most efficient type of electric motors | $245 | $750 |
$245
4,689
kWh
|
- | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $440 | $650 |
$440
8,206
kWh
|
- | |
10 | 2.2511: Insulate bare equipment | $200 | $140 |
$200
3,517
kWh
|
- | |
TOTAL RECOMMENDED | $11,978 | $17,977 |
$9,148
187,867
kWh
|
$2,830
-
MMBtu
|
||
TOTAL IMPLEMENTED | $6,638 | $7,376 |
$3,808
71,220
kWh
|
$2,830
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs